NOTE
This man page only documents the hardware-specific features of the
mge-shut driver. For information about the core driver, see nutups-
drv(8).
SUPPORTED HARDWARE
mge-shut support all recent MGE UPS models which use the SHUT (Serial
HID UPS Transfer) protocol at 2400 bps. Supported models are:
Pulsar Ellipse S,
Pulsar Ellipse USBS
Pulsar Ellipse Premium S,
Pulsar Ellipse Premium USBS
Pulsar EXtreme C,
Pulsar Esprit,
Pulsar Evolution,
NOVA AVR (Serial),
Galaxy 3000 / PW (with RS232 HID COM ports card, ref 66066).
Older models, such as Pulsar ESV+, Pulsar EX and Pulsar ES+, use the
U-Talk protocol and should use the mge-utalk driver.
EXTRA ARGUMENTS
This driver supports the following optional settings in the
ups.conf(5):
lowbatt=num
Set the low battery warning threshold at which shutdown is ini-
tiated by upsmon(8). The factory default value is 30 (in per-
centage), and only be settable depending on the exact model.
offdelay=num
Set the timer before the UPS is turned off after the kill power
command is sent (via the -k switch). The default value is 20
(in seconds), and MUST BE LOWER than ondelay.
ondelay=num
Set the timer for the UPS to switch on in case the power returns
after the kill power command had been sent but before the actual
switch off. This ensures the machines connected to the UPS are,
in all cases, rebooted after a power failure. The default value
is 3 (in 10 seconds units, which means 30 seconds), and MUST BE
GREATER than offdelay.
notification=num
Set notification type to 1 (no), 2 (light) or 3 (yes). The
AUTHOR
Arnaud Quette <arnaud.quette@free.fr> or <arnaud.quette@mgeups.com>
Philippe Marzouk <philm@users.sourceforge.net>
SEE ALSO
The core driver:
nutupsdrv(8)
Internet resources:
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
MGE UPS SYSTEMS SHUT protocol information: http://random.networkup-
stools.org/protocols/mge/
Fri Dec 16 2005 mge-shut(8)
Man(1) output converted with
man2html